Weil-McLain Boiler: Steam condensate return and feed system
Steam condensate return and feed system on a Weil-McLain boiler: Steam heating depends on enough condensate returning to keep a steady water level. Avoid adding raw makeup water. If the return is not adequate, use a low water cutoff with pump control, a condensate receiver and a condensate boiler feed pump, sized from Table 7 and Table 9.
Applies to: EG/PEG steam boilers
Common causes of steam condensate return and feed system
- Condensate return to the boiler is inadequate
- Raw makeup water being added to the boiler
How to fix steam condensate return and feed system: step by step
- Confirm condensate return is adequate for a steady water level.
- If it is not, install a low water cutoff with pump control, a condensate receiver and a condensate boiler feed pump.
- Size the receiver and feed pump from Table 9 (see the boiler feed system sizing table in this section).
- Do not use a combination condensate tank with a float-controlled return pump; the manual does not recommend it.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.