Weil-McLain Boiler: Steam boiler low water cutoff installation
Steam boiler low water cutoff installation on a Weil-McLain boiler: Water line dimensions are measured from the bottom of the boiler section leg where it rests on the floor or foundation. Probe-type and float-type low water cutoffs are installed differently. Water feeders are not recommended as the primary control; use a low water cutoff with pump controller when a condensate receiver and feed pump are used.
Applies to: EG and PEG steam boilers
How to fix steam boiler low water cutoff installation: step by step
- Measure water line dimensions from the bottom of the boiler section leg.
- For probe-type low water cutoffs, install as shown in Figure 24.
- For float-type low water cutoffs, install as shown in Figure 25.
- Install a blowdown line in the bottom of the cutoff per Figure 25 and the control maker's instructions.
- Pipe the blowdown line near the floor, close to a floor drain, to avoid burn hazards.
- Do not plug, valve or obstruct the blowdown line.
- Install the remaining controls per the control tapping table and Figure 4.
- Use a primary float LWCO or secondary manual reset LWCO with the primary probe LWCO as the control arrangement.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.