Weil-McLain Boiler: Startup verification checklist
Startup verification checklist on a Weil-McLain boiler: Commissioning items to confirm before leaving the boiler.
Applies to: SVF 1500-3000
How to fix startup verification checklist: step by step
- Confirm the control is programmed correctly and the system is filled and purged of air.
- Confirm the condensate trap is filled with water and the float is in place.
- Confirm water chemistry per page 85.
- Confirm flame and combustion are verified (page 88).
- Test space heating and DHW operation (if used) and any field limits.
- Confirm field thermostats and anticipator are set and cycle the boiler high and low.
- Measure natural gas input and check incoming gas pressure per page 47.
- Review instructions with the owner and fill in the installation certificate on page 121.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 90. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.