Weil-McLain Boiler: Skim a new steam boiler to remove oil and grease
Skim a new steam boiler to remove oil and grease on a Weil-McLain boiler: Clean newly installed steam boilers to remove oil and grease. Failure to clean can cause violent water level changes, water entering steam mains and high maintenance on strainers, traps and vents. Do not use petroleum-based compounds.
Applies to: New EG / PEG steam boilers
How to fix skim a new steam boiler to remove oil and grease: step by step
- Provide 1-1/2 in. piping from the skim tapping to a floor drain.
- Adjust the waterline to the midpoint of the skim tapping (see Figure 4, page 14).
- Fire the boiler to keep temperature below the steaming rate, following the lighting instructions.
- Feed in water to maintain water level and cycle burners to prevent steam pressure rise.
- Continue skimming until discharge is clear; this may take several hours.
- Drain the boiler; while warm but not hot, flush all interior surfaces under full pressure until drain water runs clear.
- Remove skim piping and plug the tapping.
- Close the drain cock, fill with fresh water to the waterline, then start burners and steam for 15 minutes to remove dissolved gases. Stop burners.
- Check traps and air vents for proper operation.
- Repeat the process after several weeks of operation if needed.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 boiler manual, p. 62. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.