Weil-McLain Boiler: Sizing a shared combustion air duct
Sizing a shared combustion air duct on a Weil-McLain boiler: Multiple boilers can share a combustion air manifold. Only air piping may be combined, never vent piping.
Applies to: Manifolded combustion air option
How to fix sizing a shared combustion air duct: step by step
- Provide minimum clearance to adjacent vents and grade/snow line per the figure.
- Size the duct at 1 sq in of free area per 2,000 Btuh of total input, adjusted for louver restriction.
- Quick check: total MBH input divided by 2 gives minimum duct area in sq in. Example: 3 x EVG 299 = 897 MBH, so 448.5 sq in.
- If a combustion air damper is used, wire the boilers so they cannot fire until the damper has opened.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 5-6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.