Updated · by Aurora Star Tech Inc.

Sizing a shared combustion air duct on a Weil-McLain boiler: Multiple boilers can share a combustion air manifold. Only air piping may be combined, never vent piping.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Manifolded combustion air option

How to fix sizing a shared combustion air duct: step by step

  1. Provide minimum clearance to adjacent vents and grade/snow line per the figure.
  2. Size the duct at 1 sq in of free area per 2,000 Btuh of total input, adjusted for louver restriction.
  3. Quick check: total MBH input divided by 2 gives minimum duct area in sq in. Example: 3 x EVG 299 = 897 MBH, so 448.5 sq in.
  4. If a combustion air damper is used, wire the boilers so they cannot fire until the damper has opened.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Evergreen Series 2 advanced manual, p. 5-6. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.