Updated · by Aurora Star Tech Inc.

Setting the flue collector hood, rear base and drawer assembly on a Weil-McLain boiler: On PEG boilers the flue collector hood and rear base panels come factory installed. A gas-tight seal is required at the hood and base panels to prevent flue gas spillage. On EG boilers the front base panel, burner drawer and manifold are assembled and set into the section assembly.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG and PEG boilers, burner drawer and base assembly

Common causes of setting the flue collector hood, rear base and drawer assembly

  • Broken gas-tight seal causing flue gas spillage and carbon monoxide
  • Burners not seated in the back burner support slots, or orifices not centered over the burners
  • Wrong orifice size for the input rating

How to fix setting the flue collector hood, rear base and drawer assembly: step by step

  1. Set the flue collector hood as shown and seal it with the boiler cement furnished.
  2. Fasten the rear base panel channel to the section assembly and seal along the top of the insulation panels with boiler cement (EG 30 through 75).
  3. Fasten the front base panel (6 1/8 in high) and the rear base channel to the section assembly, sealing along the top of the insulation panels.
  4. Verify the orifices against the orifice sizing table before installing.
  5. Place burners in the drawer so they sit in the slots of the back burner support with openings facing up.
  6. Slide the drawer under the front base panel and attach it to the section assembly.
  7. Level and straighten the burners so each gas orifice injects down the center of its burner.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: EG / PEG Series 7 Boiler Manual, pp. 15-16 (see Table 5 and Figures 8-11 on p. 17). Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.