Weil-McLain Boiler: Setting the boiler on its legs and leveling
Setting the boiler on its legs and leveling on a Weil-McLain boiler: Casters are only for moving the boiler into place. Front and piping-end casters swivel, middle casters are fixed. The boiler must be carried on the leveling legs, with the base at least 1-1/2 inches above the floor and wheels off the ground. Level front to back and side to side on the cover plate. For seismic or bolted installs, use the seven mounting brackets (28 holes, 3/8 inch bolts or anchors) and keep the same 1-1/2 inch minimum. Remove jacket panels to reach the leg bolts and jam nuts.
Applies to: All SVF 1500-3000 models
How to fix setting the boiler on its legs and leveling: step by step
- Roll the boiler into position and set the leg adjusters down until they touch the floor.
- Remove jacket panels as needed to reach bolt heads and jam nuts.
- Extend the legs until the base is at least 1-1/2 inches above the floor.
- Level the boiler front to back and side to side, measuring on the cover plate.
- For seismic work, bolt the seven brackets with 3/8 inch bolts or anchors, keeping the 1-1/2 inch minimum.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 1500-3000 Series 1 boiler manual, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.