Weil-McLain Boiler: Set up the boiler priorities in the Express Setup wizard
Set up the boiler priorities in the Express Setup wizard on a Weil-McLain boiler: Assign each input and output to the priority it serves, then choose the system type. Network priorities are set on the master boiler only.
Applies to: Multi-boiler and single boiler installations using the Express Setup wizard
How to fix set up the boiler priorities in the express setup wizard: step by step
- Open the Express Setup wizard and go to the priority screen.
- Pick which priority (1 to 4) each input or output will serve. Priority 1 is served first.
- Assign each priority as local (1 or 2, direct-piped to that boiler only) or network (1 or 2, any boiler on the network can satisfy it).
- Answer YES or NO to whether Network Priority 1 or 2 will be used if the screen asks.
- Select the system type for the priority (fan coil, finned tube baseboard, cast iron baseboard, cast iron radiator, radiant slab on grade, radiant thin slab, or custom).
- Set the target adjust method: NONE (fixed target at max), ODT (outdoor reset, default), or 0-10V remote target.
- Enter max and min target temperatures and the reset points, or the voltage points if 0-10V is used.
- Set the boost time, pump run options, and the max/min on time on the master boiler.
- Confirm the sequencing, rotation and timer settings for the network.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Series 2 Condensing Gas Boiler Advanced Manual, pp. 16-18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.