Weil-McLain Boiler: Separate low water cut-off installation
Separate low water cut-off installation on a Weil-McLain boiler: A separate low water cut-off is required and must be supplied by the installer, even though the control has inherent protection. The LWCO mounts on an added tee between the top pipe and the pressure sensor, using a 3/4 in female NPT port. Electrode probe type is recommended and must be designed for water.
Applies to: All ECO Tec Series 3 boilers
How to fix separate low water cut-off installation: step by step
- Install an additional tee between the top pipe and the pressure sensor.
- Mount the LWCO in the 3/4 in female NPT port location.
- Use a LWCO designed for water installations, electrode probe type recommended.
- If using the Weil-McLain LWCO kit, bundle extra wire with zip ties and keep it away from internal components.
- Wire the LWCO per the field wiring section.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Boiler Manual, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.