Weil-McLain Boiler: Select a circulator for a direct-connected DHW water heater
Select a circulator for a direct-connected DHW water heater on a Weil-McLain boiler: Size the DHW loop circulator for a water heater piped across the Ultra boiler, using the boiler head loss and piping head loss tables.
Applies to: Ultra boilers on combined space heating/DHW systems with a direct-connected water heater
How to fix select a circulator for a direct-connected dhw water heater: step by step
- Pipe the DHW tank and boiler per the suggested diagrams.
- From the water heater data, note the required boiler flow in GPM at 190°F.
- From the same data, note the water heater pressure drop in feet w.c. (this is H3).
- In the pipe sizing table, find the boiler model and select the flow rate just above the required flow.
- Read H1 (boiler head loss) and H2 (piping head loss) from that row, using the listed copper pipe size.
- Add H1 + H2 + H3 to get total head loss.
- Select a circulator that delivers the required GPM at that total head loss, using the pump curves.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.