Weil-McLain Boiler: Removing and cleaning the brazed plate heat exchanger
Removing and cleaning the brazed plate heat exchanger on a Weil-McLain boiler: The gas valve does not need to come off to remove the brazed plate heat exchanger.
Applies to: 80/110/150/199 Series 3
Common causes of removing and cleaning the brazed plate heat exchanger
- Scale deposits in the brazed plate heat exchanger
How to fix removing and cleaning the brazed plate heat exchanger: step by step
- Remove the two Allen head bolts with a 4mm Allen wrench.
- Push the brazed plate back away from the manifolds to clear the bolt bosses.
- Slide the brazed plate up and to the left and remove it from the boiler.
- Immerse the brazed plate in a chemical bath for a time shorter than the maximum given on the chemical data sheet.
- Recover the chemical into suitable containers for disposal.
- Flush the brazed plate with potable water and repeat if necessary.
- Reinstall in the same orientation.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 156. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.