Weil-McLain Boiler: Remote modulation with a 0-10 VDC input (single boiler only)
Remote modulation with a 0-10 VDC input (single boiler only) on a Weil-McLain boiler: Use an external 0-10 VDC signal to modulate a single boiler. Not supported for boilers in a network. Using this input replaces Input 1 as the heat demand. The Unity control can use 0-10 VDC for either target operation or modulation, not both.
Applies to: SVF 1500-3000 Series 1 with Unity control, single boiler
How to fix remote modulation with a 0-10 vdc input (single boiler only): step by step
- Wire the 0-10 VDC positive signal to P15 terminal 6 and common to P15 terminal 5.
- Set the single-boiler Unity control configuration (not network).
- Put the system on Priority 2 and accept the Input 1 defaults in the Wizard.
- After the Wizard, go to Assign Inputs, select Input 1, and change SOURCE from TT1 to 0-10V.
- If DHW is needed, wire the DHW aquastat to Input 2 or 3 and assign that input to Priority 1.
- Wire the system pump to Output 1 (120VAC). Output 1 follows the heat demand.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 1500-3000 Series 1 boiler manual, p. 64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.