Weil-McLain Boiler: Remote 0-10 VDC modulation input
Remote 0-10 VDC modulation input on a Weil-McLain boiler: The U-Control accepts a remote 0-10 VDC signal on P15 terminal 6 (positive) and terminal 5 (common). The boiler starts above 1.0 VDC, shuts off below 0.5 VDC, stays at low fire until 2.0 VDC, then increases firing rate up to full input at 10.0 VDC. The control still monitors temperatures using the Priority 1 settings.
Applies to: Ultra U-Control remote modulation
How to fix remote 0-10 vdc modulation input: step by step
- Connect the positive 0-10 VDC wire to P15 terminal 6.
- Connect the signal common to P15 terminal 5.
- Set the boiler as Type 4 (SHADOW) if a separate controller is providing the signal.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 98. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.