Weil-McLain Boiler: Reducing vent and air length for elbows
Reducing vent and air length for elbows on a Weil-McLain boiler: Each elbow beyond the allowed count reduces the maximum length. The allowed count is more than two elbows in the vent and one elbow in the air piping. Reduction applies to 45 and 90 degree elbows alike.
Applies to: Vent and air piping with added elbows
Common causes of reducing vent and air length for elbows
- Short-radius elbows add pressure loss and reduce allowable piping length
How to fix reducing vent and air length for elbows: step by step
- Count all elbows in the vent piping, terminations and air piping.
- If there are more than two elbows in the vent or one in the air piping, cut the maximum length for each extra elbow.
- Reduce length by 15 ft per extra elbow for polypropylene 8-inch or 10-inch.
- Reduce length by 7 ft per extra elbow for PVC 8-inch.
- Reduce length by 15 ft per extra elbow for PVC 10-inch.
- If the pipe maker's equivalent length for an elbow is longer than these values, use the pipe maker's value instead.
- Use sweep elbows wherever possible.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 Boiler Manual, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.