Weil-McLain Boiler: Recheck maximum and minimum CO2 and CO after adjustment
Recheck maximum and minimum CO2 and CO after adjustment on a Weil-McLain boiler: Confirm both firing rates after any gas valve change.
Applies to: ECO Tec Series 3 80/110/150/199
How to fix recheck maximum and minimum co2 and co after adjustment: step by step
- Turn the boiler off, then back on, and put it in Test Mode at maximum. Confirm CO2 is unchanged and CO is within limits.
- Reduce to minimum and recheck CO2 and CO.
- If CO2 and CO cannot be reached, contact your WM Technologies representative.
- Replace the test port cap (A).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 136. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.