Weil-McLain Boiler: Read the lockout history
Read the lockout history on a Weil-McLain boiler: The control stores the last three lockouts with the fault name, type, time, date, and the boiler status, temperatures, inputs and outputs at that time.
Applies to: Lockout review
How to fix read the lockout history: step by step
- Open DIAGNOSTICS and go to PAST ERRORS.
- Check CONTROL FAULTS, MANUAL RESET CNT and AUTO RESET CNT for the totals.
- Select LOCKOUT HISTORY 1 for the most recent error, then 2 and 3 for older ones.
- For each lockout, read FAULT NAME, FAULT TYPE, TIME and DATE.
- Open the Status, Temperatures, Inputs and Outputs screens to see conditions at the time of the lockout.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 82-83. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.