Weil-McLain Boiler: Re-check maximum and minimum CO2 and CO
Re-check maximum and minimum CO2 and CO on a Weil-McLain boiler: Confirm the combustion settings at both high and low fire after adjustment.
Applies to: ECO Tec Series 3 gas boilers
How to fix re-check maximum and minimum co2 and co: step by step
- Turn the boiler off, then on again, and put it in Test Mode at maximum.
- Confirm the CO2 setting has not changed and CO is within limits.
- Reduce to minimum and re-check output, confirming CO2 is unchanged and CO is within limits.
- If CO2 and CO cannot be obtained, contact WM Technologies.
- Replace the test port cap (A), see Figure 118, p. 132.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.