Weil-McLain Boiler: Protecting and capping the concentric termination during install
Protecting and capping the concentric termination during install on a Weil-McLain boiler: Blocked air passages will stop the boiler from running, and cemented parts cannot be repaired. Keep debris out during installation, and do not alter the assembly.
Applies to: 3 in or 4 in concentric termination assembly
How to fix protecting and capping the concentric termination during install: step by step
- Wrap plastic or other protection over the end of the exposed assembly before inserting it through the roof or wall.
- Do not cement the rain cap until the assembly is through the penetration and all supports are installed.
- After positioning, place the bird screen on the end of the inner pipe, then cement the rain cap in place.
- Do not cut or alter the termination assembly. A cut part cannot be cleaned and must be replaced.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 74, 76-77. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.