Weil-McLain Boiler: Probe type low water cutoff: clean and test
Probe type low water cutoff: clean and test on a Weil-McLain boiler: Periodic cleaning and function test of a probe type low water cutoff.
Applies to: Probe type low water cutoff
How to fix probe type low water cutoff: clean and test: step by step
- Turn off power to the boiler and wait 5 minutes.
- Drain water down to the bottom of the gauge glass.
- Turn power back on.
- Set the thermostat to call for heat; the red neon lamp on the low water cutoff should light.
- Wait 5 minutes; the boiler should not fire.
- Refill to the correct waterline; the red lamp should go off.
- Wait 5 minutes; the boiler should fire.
- Return the thermostat to its normal setting.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Gas-Fired Boilers User Manual 550-100-226/0425, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.