Weil-McLain Boiler: Prevent combustion air contamination
Prevent combustion air contamination on a Weil-McLain boiler: Chlorine or fluorine products in the boiler air supply form acid in the boiler and can eat through the heat exchanger. Check the intake area before you accept the install or service.
Applies to: Ultra Series 4 gas-fired water boilers, combustion air inlet and boiler room
Common causes of prevent combustion air contamination
- Spray cans with chloro/fluorocarbons, chlorine bleaches, detergents or solvents, or chlorinated cleaners near the air inlet
- Pool, laundry, dry cleaning, beauty salon, auto body or similar areas feeding the air inlet
- Refrigerant leaks, hydrochloric/muriatic acid, cements, glues or paint removers nearby
How to fix prevent combustion air contamination: step by step
- Do not operate an Ultra boiler whose combustion air inlet is in a laundry room or pool area.
- Remove any listed contaminating products from the boiler room or the air inlet area.
- If products cannot be removed, have the installer re-pipe the combustion air and vent to an uncontaminated location.
- If contaminants were present for a long time, have a technician inspect the boiler for acid corrosion.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 user's information manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.