Weil-McLain Boiler: Pre-troubleshooting checks before diagnosing a fault
Pre-troubleshooting checks before diagnosing a fault on a Weil-McLain boiler: Basic checks before working on the control or components. Turn off power before servicing and never jumper a device except for momentary testing.
Applies to: 80/110/150/199 Series 3
How to fix pre-troubleshooting checks before diagnosing a fault: step by step
- Use Figure 139 tools and kits (see the tools tip).
- Measure supply voltage to the boiler: 120VAC, with a range of 102VAC minimum to 132VAC maximum.
- Review the control's last six lockout histories in the DIAGNOSTICS menu under FAULT HISTORY. Record Ignition Retries, Manual Reset Count and Auto Reset Count.
- Confirm the thermostat is calling for heat and its contacts, including any zone controls, are closed. Check for 24VAC between the thermostat wire nuts and ground.
- Confirm all external limit controls are installed and closed, or temporarily jumpered for testing only.
- Confirm connectors are fully seated at the module and at the originating control.
- Check gas pressures. Lockup pressure with no flow must not exceed 14 in w.c. (355 mm). On high fire, inlet pressure must not drop below the minimum on page 24.
- Record the boiler size and CP number from the right side exterior of the jacket before calling for assistance.
- Reinstall the jacket door securely after servicing so the boiler does not draw room air.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 159. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.