Weil-McLain Boiler: Piping multiple boilers on Easy-Fit manifolds
Piping multiple boilers on Easy-Fit manifolds on a Weil-McLain boiler: Layout rules for header and manifold piping when several Ultra boilers share one system.
Applies to: Multiple Ultra boiler installations
How to fix piping multiple boilers on easy-fit manifolds: step by step
- Size the main header and Easy-Fit manifolds for total connected boiler output. For replacement boilers, keep the existing supply and return sizes.
- Place manifold connections near the midpoint of the boilers.
- Put the return manifold on the return side of the main and the supply manifold on the supply side.
- Install a flow/check valve in each boiler supply.
- Install an isolation valve on the supply and return of each boiler if used.
- Install the main air eliminator and primary circulator in the supply piping; place the expansion tank on the suction side of the system circulator.
- Strap supply and return sensors to the lines at least 6 pipe diameters (no more than 3 feet) from the boiler connection tees.
- Where isolation valves are used, check local code for individual low water cutoffs and limits on each boiler. The U-Control proves water level with a dual temperature sensor in the heat exchanger.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, pp. 60–62. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.