Weil-McLain Boiler: Pilot lights, main valve will not come on (pilot and gas valve check)

Updated · by Aurora Star Tech Inc.

Pilot lights, main valve will not come on (pilot and gas valve check) on a Weil-McLain boiler: Chart 5 for steam and water EG/PEG boilers, with or without vent damper. Confirms pilot gas flow, spark gap and gas valve operation.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG and PEG Series 7 steam and water boilers, natural gas

Common causes of pilot lights, main valve will not come on (pilot and gas valve check)

  • Loose pilot valve connections
  • Manual hand valve closed
  • Inlet gas pressure out of range
  • Spark gap incorrect or not in pilot gas stream
  • Gas cock off or pilot line kinked or blocked
  • Clogged pilot orifice
  • Faulty gas valve

How to fix pilot lights, main valve will not come on (pilot and gas valve check): step by step

  1. Block any draft around the boiler.
  2. Check that the pilot valve connections are correct and securely fastened.
  3. Open the manual hand valve.
  4. Check that inlet gas pressure is at least 5.0 in. w.c. and not more than 14.0 in. w.c. If not, contact the gas supplier to correct pressure.
  5. Check that the spark gap is 0.125 in. and located in the pilot gas stream. If not, replace the pilot assembly.
  6. Check for gas at the pilot burner assembly: remove the wire to MV on the ignition control, then use a match taped to a long screwdriver or pilot lighter rod to light the pilot manually.
  7. If the pilot lights, reconnect securely to terminals PV and MV/PV on the ignition control and open the manual hand valve.
  8. If the pilot does not light, check that the gas cock is in the ON position and the pilot line is not kinked or obstructed, and check for a clean pilot orifice.
  9. If the orifice is clean and gas flows, replace the gas valve.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: EG/PEG Series 7 boiler manual, p. 81. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.