Weil-McLain Boiler: Pilot lights, main valve will not come on (ignition control and gas path check)
Pilot lights, main valve will not come on (ignition control and gas path check) on a Weil-McLain boiler: Chart 3 for steam and water EG/PEG boilers. Work through the checks in order, starting with the control's 24VAC supply and gas pressure, then the spark, sense circuit and flame signal.
Applies to: EG and PEG Series 7 steam and water boilers, natural gas, spark-ignited pilot
Common causes of pilot lights, main valve will not come on (ignition control and gas path check)
- Ignition control has no 24VAC between MV and PV
- Inlet gas pressure outside 5.0 to 14.0 in. w.c.
- Loose main valve wiring
- Spark does not stop after pilot is established
- Sense wire wrapped on pipes or accessories, or not secure at sense terminal and pilot assembly
- Cracked ceramic on sensing probe
- Sense wire or probe shorted to metal
- Weak flame signal
How to fix pilot lights, main valve will not come on (ignition control and gas path check): step by step
- Check for 24VAC between terminals MV and PV on the ignition control. If there is none, replace the ignition control.
- Check inlet gas pressure. It must be at least 5.0 in. w.c. and not more than 14.0 in. w.c. If it is out of range, contact the gas supplier to correct pressure.
- Confirm main valve wiring is secure at the terminals. Correct any wiring problem.
- Energize the system and check that the spark stops a few seconds after the pilot is established. If it keeps sparking, replace the ignition control.
- Check that the sense wire is not wrapped around any pipe or accessory and is firmly attached to the sense terminal and pilot assembly.
- Inspect the sensing probe ceramic for cracks. Replace the pilot assembly if cracked.
- Check that the sense wire or probe is not shorted to a metal surface. Check sense wire continuity and insulation condition. Replace the wire if either is bad.
- Measure flame signal: detach the sense lead from the ignition control, connect the microammeter negative lead to the sense terminal, the positive lead to the sense wire from the pilot, and disconnect the main valve lead from MV. Energize and confirm the pilot lights. The reading must meet the minimum for the control (1.0 microamp for Honeywell/Resideo S8620C, 0.1 microamp for United Technologies 1003-611A).
- If the flame signal is low, check gas pressure, clean the pilot assembly, tighten mechanical and electrical connections, check system grounding (see Chart 4), then re-measure.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.