Weil-McLain Boiler: Nuisance shutdowns: check system grounding
Nuisance shutdowns: check system grounding on a Weil-McLain boiler: Chart 4. The pilot assembly and ignition control must share a common ground with the main burner. Poor or erratic ground commonly causes nuisance shutdowns.
Applies to: EG and PEG Series 7 boilers with pilot ignition
Common causes of nuisance shutdowns: check system grounding
- Poor metal-to-metal contact at pilot bracket, main burner or burner rest
- Loose or damaged ground lead at ignition control or transformer
- Damaged ground wire
How to fix nuisance shutdowns: check system grounding: step by step
- Turn off power before working on the controls.
- Check for good metal-to-metal contact between the pilot burner bracket and the main burner, and between the main burner and the burner rest.
- Check the ground lead from the GND (Burner) terminal on the ignition control to the ignition control mounting screw.
- Check the ground lead from the C terminal on the transformer to the transformer case ground.
- Make sure all connections are clean and tight.
- If a wire is damaged or deteriorated, replace it with 18 gauge moisture-resistant thermoplastic wire rated 105°C minimum.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG/PEG Series 7 boiler manual, p. 81. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.