No spark, system does not work (without vent damper, Chart 1) on a Weil-McLain boiler: Troubleshooting chart for a no-spark condition on steam boilers without a vent damper. The flowchart text is out of order in the extracted pages, so the sequence below follows the chart's checks.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG and PEG steam boilers without vent damper

Common causes of no spark, system does not work (without vent damper, chart 1)

  • Vent damper plug missing (with damper systems)
  • Ground wiring faulty
  • No 24 VAC at the ignition control
  • Open thermostat, circulator relay, spill switch, rollout fuse, LWCO or limit contacts
  • Spark wire, electrode or gap faulty

How to fix no spark, system does not work (without vent damper, chart 1): step by step

  1. Turn off supply voltage before checking connections.
  2. Check that the vent damper plug is in place. If not, replace the damper plug and retest.
  3. Visually check the ground wire from GND (Burner) to the ignition control mounting screw, and from transformer terminal C to case ground.
  4. Check for 24 VAC across terminals 24V and 24V(GND). If absent, check for an open thermostat, circulator relay, loose wires, defective spill switch or rollout thermal fuse, or open LWCO or limit contacts. If LWCO, spill switch or rollout contacts are open, find and correct the cause before continuing.
  5. Open the thermostat contacts for 15 seconds, then close them, and check for 24 VAC across PV and MV/PV.
  6. Check that the spark wire is securely connected to the spark transformer and is not cut, brittle, burned or cracked.
  7. Check that the spark electrode ceramic is not cracked.
  8. Check that the spark gap is 0.125 in and located in the pilot gas stream.
  9. If the wiring and parts check out, replace the pilot assembly or ignition control as indicated, turn on supply voltage, and run several complete heat cycles.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: EG / PEG Series 7 Boiler Manual, p. 78. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.