Updated · by Aurora Star Tech Inc.

No display and blower running at full speed on a Weil-McLain boiler: Control is not getting 24 V power.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra 80, 105, 155, 230, 299, 399

Common causes of no display and blower running at full speed

  • Short circuit or incorrect wiring
  • Blown 3 A low voltage fuse
  • Transformer wiring wrong or transformer not outputting 24 VAC

How to fix no display and blower running at full speed: step by step

  1. Check wiring for shorts or errors; correct it to the wiring diagram, including the transformer connection to the U-Control.
  2. Check the 3 A low voltage fuse (page 116) and replace it with the proper part if blown. If it blows again, recheck wiring.
  3. Check transformer output. If it receives 120 VAC but gives no 24 VAC, replace the transformer.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Ultra Series 4 gas-fired water boiler manual, p. 118. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.