Weil-McLain Boiler: Network priority is set from the Master only
Network priority is set from the Master only on a Weil-McLain boiler: Each of the four inputs on the Master or any shadow boiler can be assigned as Network Priority 1 or 2, or Local Priority 1 or 2. Network priority settings are common to all boilers and can only be changed at the Master. When a Local Priority input closes, that boiler modulates from its own inlet and outlet sensors instead of being controlled by the Master.
Applies to: Multiple boiler networks on Evergreen Pro control
How to fix network priority is set from the master only: step by step
- Make all Network Priority 1 and 2 changes at the Master boiler.
- Assign Local Priority inputs on the boiler that should respond to them locally.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 63-64. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.