Weil-McLain Boiler: Monthly condensate drain and trap check
Monthly condensate drain and trap check on a Weil-McLain boiler: With the boiler running, flue gas must not come from the condensate drain or tee. A dry trap lets flue products into the boiler room.
Applies to: Ultra Series 4 condensate drain line, condensate tee and trap
Common causes of monthly condensate drain and trap check
- Dry condensate trap (not enough condensate from the Ultra vent)
- Obstructed condensate drain line
How to fix monthly condensate drain and trap check: step by step
- While the boiler runs, hold a hand near the discharge end of the condensate drain tubing and the open top of the condensate tee. Check for flue gas escaping.
- If flue gas escapes, the trap is dry. Refill the trap using the procedure below.
- To check for an obstruction, slowly pour water into the top of the PVC tee on the boiler side. Water should run out the end of the drain line.
- If water does not run out, call a qualified service technician to clean or replace the condensate drain line.
- To refill the trap, temporarily plug the drain line end. Slowly pour water into the 1/2 inch plastic tee on the boiler right side until it fills the drain line and overflows into the trap tubing.
- Stop when water reaches the top of the 1/2 inch tee. Remove the temporary plug from the drain line end.
- If the trap keeps running dry, call a qualified service technician to inspect the boiler and condensate line.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 user's information manual, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.