Weil-McLain Boiler: Measure natural gas input
Measure natural gas input on a Weil-McLain boiler: Confirm the calculated input is close to the rating label.
Applies to: ECO Tec Series 3 80/110/150/199
How to fix measure natural gas input: step by step
- Operate the boiler 10 minutes and turn off other gas appliances.
- At the natural gas meter, time how many seconds one cubic foot of gas takes.
- Calculate input: 3600 x 1000 divided by the number of seconds, giving Btuh.
- Confirm the Btuh result approximately matches the input rating on the boiler rating label.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 135. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.