Weil-McLain Boiler: Massachusetts venting: CO detectors and vent warning sign
Massachusetts venting: CO detectors and vent warning sign on a Weil-McLain boiler: Applies to sidewall horizontally vented gas equipment where the vent termination is less than 7 feet above finished grade, in dwellings used for residential purposes.
Applies to: Sidewall horizontally vented gas equipment in Massachusetts
How to fix massachusetts venting: co detectors and vent warning sign: step by step
- Confirm a hard-wired carbon monoxide detector with alarm and battery backup is installed on the floor level where the gas equipment is located.
- Confirm a battery-operated or hard-wired CO detector with alarm is installed on each additional level of the building served.
- In a crawl space or attic installation, the detector may be installed on the next adjacent floor level.
- If the requirements cannot be met at completion, the owner has 30 days to comply, and a battery-operated CO detector with alarm must be installed during that time.
- Use CO detectors that comply with NFPA 720 and are ANSI/UL 2034 listed and IAS certified.
- Mount a metal or plastic sign on the building exterior at least 8 feet above grade, directly in line with the exhaust vent terminal. Lettering must be at least 1/2 inch and read: GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
- Leave all installation, venting and parts instructions with the appliance at completion.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.