Updated · by Aurora Star Tech Inc.

Low water cutoff wiring on a Weil-McLain boiler: Supplied LWCO sensor is recommended. An alternate LWCO must use an isolated contact.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Evergreen 110/155/220/299/300/399

How to fix low water cutoff wiring: step by step

  1. Remove the factory jumper on J9 before connecting the supplied LWCO sensor to J9.
  2. For the Weil-McLain LWCO kit, connect it to J21 using the harness, as shown in the control wiring diagram.
  3. For another LWCO device, use only one with an isolated contact, and connect it as shown in the wiring diagram.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 51. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.