Weil-McLain Boiler: Low flame signal troubleshooting
Low flame signal troubleshooting on a Weil-McLain boiler: Use when the running flame signal stays low.
Applies to: ECO Tec Series 3 gas boilers
Common causes of low flame signal troubleshooting
- Fouled ignition electrode
- Damaged electrode insulation
- Poor ground wiring
- Fouled heat exchanger
- Venting or combustion problem
How to fix low flame signal troubleshooting: step by step
- Remove and inspect the ignition electrode (p. 141).
- Clean the electrode if needed.
- If cleaning does not help and ground wiring and continuity are good, replace the ignition electrode.
- If the signal is still low, inspect the vent and air piping.
- Check combustion values.
- Inspect and clean the heat exchanger per the cover plate procedure (p. 151).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 142. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.