Weil-McLain Boiler: Locating the direct vent air inlet termination
Locating the direct vent air inlet termination on a Weil-McLain boiler: Pick the air inlet location so it is clear of debris, plants and wind eddies, and is far enough from other vents and openings.
Applies to: Ultra boilers, direct vent vertical vent / sidewall air
Common causes of locating the direct vent air inlet termination
- Air inlet blocked by plants, leaves, snow or sediment
- Air inlet placed where wind eddies or exhaust from other appliances can recirculate into it
- Air inlet too close to another appliance or building vent outlet
How to fix locating the direct vent air inlet termination: step by step
- Use a down-turned air inlet elbow, with the left-side layout unless clearance to grade or snow line fails, then use the raised right-side layout.
- Keep the air inlet at least 12 inches below and at least 12 inches horizontally from any appliance or building vent outlet.
- Keep the air inlet away from inside building corners, window wells, stairwells, alcoves, courtyards and recessed areas.
- Keep the termination away from plants that could grow into it.
- Protect the termination from stones, balls and leaf or sediment buildup.
- Secure air pipe runs up the wall with braces no more than 24 inches apart.
- For Canadian installs, meet CSA B149.1 or B149.2 clearances.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.