Weil-McLain Boiler: Limit controls and low water cutoff
Limit controls and low water cutoff on a Weil-McLain boiler: The control module has temperature-based high limit and operating limit control, certified to UL353 and ASME CSD-1 and Section IV. The operating limit set point equals supply maximum temperature plus the off differential. The control has two sets of limit contacts: one resets automatically and the other needs manual reset. Low-temperature circuits such as radiant slab should be protected by limits wired to a manual or automatic reset circuit. The low water cutoff is factory installed on the supply outlet pipe at the back of the heat exchanger, has a push-to-test button, and resets manually from the control display (MANUAL RESET).
Applies to: All SVF 1500-3000 models
How to fix limit controls and low water cutoff: step by step
- Set the operating limit to supply maximum temperature plus the off differential.
- Wire low-temperature circuits to a limit with manual or automatic reset, per page 49.
- Press the low water cutoff test button to check it.
- Reset a tripped low water cutoff through the display using MANUAL RESET.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 1500-3000 Series 1 boiler manual, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.