Weil-McLain Boiler: Isolation heat exchanger piping for multiple boilers (Example C)
Isolation heat exchanger piping for multiple boilers (Example C) on a Weil-McLain boiler: The boilers are piped primary/secondary, with each boiler in a secondary loop. The heat exchanger shell side and the heating system side each need their own expansion tank. The heating system also needs its own relief valve. Piping, pumps and sizing for the heat exchanger come from the heat exchanger manufacturer.
Applies to: Example C multi-boiler with isolation heat exchanger
How to fix isolation heat exchanger piping for multiple boilers (example c): step by step
- Pipe each boiler in a secondary loop, primary/secondary as shown.
- Give the heat exchanger shell-side circuit its own expansion tank.
- Give the heating system circuit its own expansion tank and its own relief valve.
- Size each circulator for the required flow.
- Get heat exchanger sizing and shell-side and tube-side piping from the heat exchanger manufacturer.
- Confirm tube-side flow and temperatures meet the heating system requirements.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Series 2 Condensing Gas Boiler Advanced Manual, p. 26-27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.