Weil-McLain Boiler: Installing the relief valve and discharge piping
Installing the relief valve and discharge piping on a Weil-McLain boiler: The relief valve is shipped loose and goes in the 1-1/4 inch coupling (SVF 1500/2000) or 2 inch coupling (SVF 2500/3000) on top of the supply outlet pipe. The discharge must run to a safe location that will not freeze. Discharge line must be as short as possible, the same size as the valve outlet, pitched down from the valve, end plain (not threaded) at a material rated for 375 °F or higher, and end at least 6 inches above a floor drain where discharge is visible. No shutoff valve may be placed between the relief valve and boiler or in the discharge line, and nothing may obstruct the line. After filling and pressurizing, lift the lever to test that the valve discharges freely; replace the valve if it fails.
Applies to: All SVF 1500-3000 models
How to fix installing the relief valve and discharge piping: step by step
- Install the relief valve in the 1-1/4 inch (SVF 1500/2000) or 2 inch (SVF 2500/3000) coupling on top of the supply pipe.
- Pipe the discharge downward, short and full size, ending plain at least 6 inches above a visible floor drain.
- Confirm no shutoff valve or obstruction exists in the discharge line or between the valve and boiler.
- After filling and pressurizing, lift the lever and confirm free discharge; replace the valve if it does not operate.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF 1500-3000 Series 1 boiler manual, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.