Weil-McLain Boiler: Install the condensate trap
Install the condensate trap on a Weil-McLain boiler: Assemble the trap so the float is in place and the connections are sealed.
Applies to: SVF 1500-3000
How to fix install the condensate trap: step by step
- Insert the 3/4 in PVC elbow through the trap inlet connection ferrule nut.
- Slide the trap inlet gasket up onto the 3/4 in PVC elbow.
- Confirm the trap float is in place.
- Tighten the inlet ferrule nut fully onto the trap.
- Slide the 1 in Fernco fitting onto the 3/4 in elbow and tighten the hose clamp with a 5/16 in nut driver or flat screwdriver.
- Confirm the bottom trap connection is fully tight.
- Slide the trap onto the heat exchanger condensate drain and tighten its hose clamp.
- Secure the trap bracket to the boiler base.
- Secure the trap to the bracket with the U-bolt.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 46. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.