Weil-McLain Boiler: Install system supply and return temperature sensors
Install system supply and return temperature sensors on a Weil-McLain boiler: Recommended for primary/secondary piping. Required for proper control.
Applies to: ECO Tec Series 3 primary/secondary systems
How to fix install system supply and return temperature sensors: step by step
- Use two strap-on sensors (separate kit). For pipe larger than 5 in. or non-metallic pipe, use immersion sensors.
- Attach one sensor to the system supply piping and one to the system return piping.
- Locate the supply sensor at least six pipe diameters, but no more than 3 ft, downstream from the boiler connection.
- Wire the return sensor to J19 pins 1 and 2.
- Wire the supply sensor to J19 pins 3 and 4.
- Thermostat wire can be used for the sensor leads.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.