Weil-McLain Boiler: Install flow switch or combustion air damper proof of closure
Install flow switch or combustion air damper proof of closure on a Weil-McLain boiler: Remove the J18 jumper and wire the device as shown in the wiring diagram. Devices must provide isolated contacts.
Applies to: ECO Tec Series 3 all models
How to fix install flow switch or combustion air damper proof of closure: step by step
- Remove the jumper on connector J18.
- Wire the flow switch and/or combustion air damper end switch in series to J18 as shown.
- For a CAD interlock, assign INPUT 3 as an AUX PUMP/OUTPUT function.
- Set the AUX PUMP/OUTPUT operating mode to local or System Damper so the damper opens whenever the boiler is called to fire.
- Connect OUTPUT 3 (120VAC) to the damper motor. Use an isolation relay if the damper needs another voltage or more than 2.2 A.
- For multi-boiler CAD interlock, wire all proof of closure inputs in series with the end point devices and each boiler's closure switch input.
- No control settings are required for a flow switch alone.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.