Weil-McLain Boiler: Indirect DHW aquastat wiring for priority
Indirect DHW aquastat wiring for priority on a Weil-McLain boiler: Heat only and combi models use different inputs for indirect DHW.
Applies to: ECO Tec Series 3 heat only and combi models
How to fix indirect dhw aquastat wiring for priority: step by step
- Heat only: connect the DHW aquastat to any one of the four input and output pairs. Assign it to PRIORITY 1 in the WIZARD or System Settings menu.
- Combi: connect the DHW aquastat to Input 2 or Input 3. Assign it to PRIORITY 2 in the WIZARD or System Settings menu.
- On combi, the internal combi DHW is PRIORITY 1 and the indirect tank is PRIORITY 2.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 68-69. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.