Weil-McLain Boiler: Indirect DHW aquastat wiring
Indirect DHW aquastat wiring on a Weil-McLain boiler: The DHW aquastat can go on any one input/output pair. That input must be assigned to Priority 1.
Applies to: Evergreen 110/155/220/299/300/399
How to fix indirect dhw aquastat wiring: step by step
- Wire the DHW aquastat contact to any one of the four inputs.
- Wire the DHW pump or valve to the matching output.
- Assign that input to Priority 1 in the Wizard or manually in the System Settings menu.
- Check that Priority 1 settings suit the indirect tank, since its defaults are set for direct-piped indirect DHW.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Series 2 Condensing Gas Boiler Advanced Manual, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.