Weil-McLain Boiler: Ignition electrode and ignition wiring check
Ignition electrode and ignition wiring check on a Weil-McLain boiler: Annual check of the ignitor, ignition cable and ground wiring.
Applies to: Ultra Series 4 boilers
Common causes of ignition electrode and ignition wiring check
- White oxide buildup on the electrode
- Worn or damaged ignitor insulation
- Poor ground continuity
How to fix ignition electrode and ignition wiring check: step by step
- Remove the ignition electrode from the heat exchanger access cover.
- Clean white oxides off with steel wool. If it cannot be cleaned satisfactorily, replace the ignitor.
- Reinstall the electrode with its gasket in good condition and correctly positioned.
- Make sure the two electrodes are parallel.
- Measure ignition cable resistance. A good cable reads 900 to 1000 ohms. Replace if not in range.
- Inspect the ground wire from the heat exchanger access cover to the ground terminal strip.
- Check ground continuity with a continuity meter. Replace ground wires if results are not satisfactory.
- Verify all wiring is in good condition and securely attached.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 gas-fired water boiler manual, p. 111-112. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.