Weil-McLain Boiler: Hydrostatic pressure test of boiler water side
Hydrostatic pressure test of boiler water side on a Weil-McLain boiler: Pressure test the boiler before connecting water or gas piping and before the electrical supply is connected. Relief valve is installed only after the test.
Applies to: ECO Tec 80/110/150/199 Series 3
How to fix hydrostatic pressure test of boiler water side: step by step
- Install 1/2 in reducer bushings (150/199), reducing tees and close nipples as shown in the piping figure, before the relief valve is fitted.
- Apply pipe dope sparingly to all fittings.
- Temporarily install a 3/4 in NPT pipe cap in the air elimination/relief valve water pipe connection.
- Install the pressure/temperature gauge on the reducing tee.
- Provide two shut-off valves and two close nipples (1 in NPT on 80/110, 1-1/4 in NPT on 150/199), plus the 3/4 in pipe cap.
- Close the boiler drain valve. Connect a hose from fresh water to the drain valve.
- Close isolation valve on the return, leave the supply isolation valve open, and crack the 3/4 in cap slightly.
- Slowly open the drain valve and fresh water supply to fill the boiler. Tighten the cap when water seeps from it.
- Continue filling until water flows from the supply isolation valve, then close it.
- Raise pressure to the test value (see setting table) by opening the drain valve as needed.
- Hold test pressure for 10 minutes. Do not leave the boiler unattended.
- Confirm pressure stays constant and check all joints for leaks. Repair any leak at once.
- Drain the boiler, remove the test fittings and cap, then install the relief valve, tee and elbow.
- Dry any water that got into electronic components, including the boiler control.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Boiler Manual, p. 17-18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.