Updated · by Aurora Star Tech Inc.

Hydrostatic pressure test before piping and wiring on a Weil-McLain boiler: Pressure test the boiler before connecting water, gas or electrical supply. The factory test is 1.5 times the maximum allowable working pressure. The on-site test pressure is 1.5 times the relief valve setting that will be installed. The relief valve is not installed until testing is done. Purge all air from the heat exchanger before testing. Do not leave the boiler unattended during a cold water fill. Do not use petroleum-based cleaners or sealants.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All SVF 1500-3000 models

How to fix hydrostatic pressure test before piping and wiring: step by step

  1. Do not install the relief valve until testing is finished.
  2. Attach blind flanges with a nipple and valve at the supply and return, plus a water supply, hand pump and drain line.
  3. Remove the shipped P/T gauge, then remove the factory plug from the 1/4 inch tap on the supply pipe and install the gauge with pipe dope.
  4. Plug the relief valve nipple (1-1/4 inch FNPT on SVF 1500/2000, 2 inch FNPT on SVF 2500/3000).
  5. If the test exceeds 160 psig, remove the automatic air vent and install a 1/2 inch NPT plug.
  6. Open the supply and return shutoff valves and let water fill from the bottom until air exits the top. Ensure all air is out, then close the top valve.
  7. Close the water supply, raise pressure with the hand pump to the test value, then close the shutoff valve.
  8. Hold the test pressure for 10 minutes and confirm the gauge reading stays steady.
  9. Check threaded joints and repair leaks. If the heat exchanger leaks, contact Weil-McLain.
  10. Release pressure and drain safely, then reinstall the automatic air vent and P/T gauge if they were removed.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF 1500-3000 Series 1 boiler manual, p. 12-13. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.