Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Boiler: High altitude adjustment

Updated · by Aurora Star Tech Inc.

High altitude adjustment on a Weil-McLain boiler: Derate rules and CO2 adjustment at altitude.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 gas boilers

How to fix high altitude adjustment: step by step

  1. Set the correct altitude in the boiler setup menu; the control adjusts low, ignition and high fire rates.
  2. At 2500 ft and above, adjust CO2 manually per the gas valve procedure on p. 135.
  3. Use the CO2 settings for your gas type and altitude in Figure 128, p. 148.
  4. In the USA, input rates are derated 4% per 1,000 ft above sea level beyond 2,000 ft.
  5. In Canada, input is derated 10% for 2,000 to 4,500 ft; above 4,500 ft follow provincial authority and local codes.
  6. Above 11,000 ft, contact WM Technologies Technical Support.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: ECO Tec series 3 boiler manual, p. 143. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977