Gas valve leakage testing on a Weil-McLain boiler: Test each gas valve solenoid on its own. Do not connect a manometer to either gas valve.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 1500-3000

How to fix gas valve leakage testing: step by step

  1. Do not connect a manometer to the manual or automatic gas valve; blower vacuum can draw fluid into the gas line.
  2. Follow the gas valve manufacturer's leak test procedure.
  3. Open the Gas Valve Test Screen from the control menu (see page 71).
  4. Highlight Open Gas Valve 1 and press enter/save.
  5. Give the boiler a call for heat. Only gas valve 1 opens.
  6. After gas valve 1 opens, end the call for heat.
  7. Repeat for Open Gas Valve 2.
  8. Exit with the back button to restore both valves for normal calls for heat.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

Source: SVF Series 1 boiler manual, p. 90. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.