Weil-McLain Boiler: Gas supply piping cautions
Gas supply piping cautions on a Weil-McLain boiler: Key gas piping rules from the install section.
Applies to: SVF 1500-3000
How to fix gas supply piping cautions: step by step
- Install a union for servicing where needed and a manual shutoff valve within 6 ft of the boiler.
- In Canada, the installer must identify the manual gas valve.
- Support gas piping with hangers, not with the boiler or its accessories.
- Use two wrenches when tightening gas piping at the boiler so the boiler connection does not turn.
- Use pipe dope that works with propane, applied lightly to male threads only.
- These boilers ship set for natural gas only. Install the propane conversion kit before connecting propane (see page 12).
- Use a 100% lock-up gas pressure regulator (ANSI Z21.80) if inlet pressure can exceed 14 in w.c.
- Set the lock-up regulator for inlet pressure below 10 in w.c. with the boiler at minimum input so there is margin under the high gas pressure switch.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.