Gas leak testing and pipe dope on a Weil-McLain boiler: Use bubble test only and never an open flame. Above 13 in w.c. test pressure, disconnect the boiler and gas valve from the line. Below 13 in w.c., close the manual main shutoff valve.
Applies to: Gas piping at Ultra boilers
How to fix gas leak testing and pipe dope: step by step
- Use a bubble test on all gas connections.
- For pressure tests below 13 in w.c., close the manual main shutoff valve.
- For pressure tests above 13 in w.c., disconnect the boiler and gas valve from the supply piping.
- Use pipe dope compatible with propane, applied sparingly only to the male threads so it does not block gas flow.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain Ultra Series 4 boiler manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.