Weil-McLain Boiler: Freeze protection operation
Freeze protection operation on a Weil-McLain boiler: With freeze protection enabled, the control fires the boiler at low fire and starts the selected circulators when heat exchanger sensors read below 45 °F. The burner starts if temperature falls below 40 °F. Circulators and burner stop when temperature rises above 48 °F.
Applies to: SVF Series 1, single boiler in Basic mode
How to fix freeze protection operation: step by step
- Enable FREEZE PROTECT CIRCS in the BOILER SETTINGS menu.
- Choose which circulators should run during freeze protection.
- Confirm the heat exchanger sensors read correctly in DIAGNOSTICS > TEMPERATURES.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 75. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.